Why work with us?

With over 20 years of bricklaying experience, the JRC team has built a strong reputation for cost effective and professional bricklaying solutions. We are fully licensed and insured, and our Melbourne bricklayers deliver specialist bricklaying and blocklaying services throughout the South Eastern Suburbs of Melbourne.

JRC have a demonstrated ability to run multiple projects and always supply enough labour to meet and exceed programme deadlines.

We're happy to travel

From Wantirna to Werribee we cover the Greater Melbourne area and continue to travel to do what we love. No job is too small or too big. We'll be there on time and with a professional approach to any job.

Services

We offer an extensive list of services to suit all requirements.

Bricklaying

At JRC our team of highly skilled and experienced tradesmen are capable with all aspects of Brickwork construction. We have the skills and processes in place to meet your exact requirements. We have a proven track record in the delivery of technically challenging projects. You will find our team easily accessible and willing to give advice through to the completion of your project.

Blocklaying

At JRC we have laid hundreds of thousands of square metres of perfect blockwork.

We have an experienced and fully trained workforce committed to providing quality workmanship whilst exceeding client expectations, delivered on time and on budget, within a safe environment.

JRC know what is expected of us and more importantly, our clients know what to expect from us, a consistent and professionally delivered service with a name built on honesty and quality.

We will service anywhere in Melbourne:

  • Sandringham
  • Caufield
  • Brighton
  • Elsternwick
  • Frankston
  • Cranbourne
  • Berwick
  • Pakenham
  • Dandenong
  • Belgrave
  • Bayswater
  • Wantirna

P  EI cos  (15.22) Power Factor. The term cos  in Eq. (15.22) is called the power factor of the circuit. Because it is always less than 1, it is usually expressed as a percentage. Low power factor results in high current, which requires high fuse, switch, and circuit-breaker ratings and larger wiring. Induction motors and certain electricdischarge- lamp ballasts are a common cause of low power factor. Since they are both inductive reactances (coils), the low power factor can be corrected by inserting capacitive reactances in the circuit to balance the inductive effects. This can be done with capacitors that are available commercially in standard kilovolt-ampere, kVA, capacities. For example, a 120-V, 600-kVA circuit with a 50% power factor has a current of 5000 A. The actual power expended is only 300 kW, but the wire, switches, and circuit breakers must be sized for 5000 A. If a capacitor with a 300-kVA rating is wired into the circuit, the current is reduced to 2500 A, and the wiring, switches, and circuit breakers may be sized accordingly. Conversion of AC to DC. Alternating current has the advantage of being convertible to high voltages by transformers. High voltages are desired for longdistance transmission. For these reasons, utilities produce and sell alternating current. However, many applications requiring accurate speed control need direct-current motors, for example, building elevators and railroad motors, including subways. In buildings, ac may be converted to dc by use of an ac motor to drive a dc generator, which, in turn, provides the power for a dc motor. The ac motor and dc generator are called a motor-generator set. Another device used to convert ac to dc is a rectifier. This device allows current to flow in one direction but cuts off the sine wave in the opposite direction. The current obtained from the motor-generator set described previously is a similar unidirectional current of varying instantaneous value. The only truly nonvarying direct current is obtained from batteries. However, output filters can be added to rectifiers to reduce the amount of voltage variation to nearly zero. In most cases this is acceptable, and using a rectifier as a dc source eliminates the weight, cost, and hazards involved with large storage batteries. Single-Phase and Multi-Phase Systems. A single-phase ac circuit requires two wires, just like a dc circuit. One wire is the live wire, and the other is the neutral, so called because it is usually grounded (Fig. 15.3a). A voltage commonly used in the United States is 240 V, single-phase, two-wire, which is obtained from the two terminals of the secondary coil of transformers fed from utility high-voltage lines. If a third wire is connected to the midpoint of the FIGURE 15.3 Examples of circuit wiring: (a) single-phase, two-wire circuit; (b) two-phase, three-wire circuit; (c) three-phase, four-wire circuit; (d ) current In in the neutral wire of the three-phase circuit is the phasor sum of the currents in the phase legs. secondary coil as a neutral, the voltage between either of the two terminal wires and the neutral will be 120 V (Fig. 15.3b). This voltage, 120/240 V, single-phase, three-wire, is the voltage used for most residential electrical services. The currents in the two terminal wires are 180 apart in phase. The neutral current from each is also 180 apart. These two currents, traveling in the same neutral wire, offset each other because of the phase difference. If the load currents in the two terminal wires are equal, the currents in the neutral will become zero. Though there is a phase difference between the two live wires, this is still considered as a single-phase system, designated as single-phase, three-wire. An outdated voltage system that may be encountered in renovation work is the two-phase system in which the live wires are 90 apart in phase. There are actually two types of two-phase systems, two-phase three-wire and two-phase five-wire. In a similar way, three-phase electric service can be obtained directly from the utility company with three live wires and a grounded neutral (Fig. 15.3c). The currents in the three live wires, as well as their respective return flows in the neutral, are 120 apart in phase. If the currents are equal in the three live wires, the current in the neutral will be zero. If the phase currents are not equal, the current in the neutral will be the phasor sum of the phase currents (Fig. 15.3d). In many two-phase or three-phase systems, it is necessary therefore to balance the single-phase loads on each wire as much as possible. When the current in the neutral is zero, there is no voltage drop in the return circuit. Any voltage drop in the neutral subtracts from the voltage on the single-phase wires and affects the loads on these circuits. The voltage drop times the current flowing in the neutral times the cosine of the phase angle is the power consumed in the neutral wire, and this adds to the total metered power on the utility bill. Electric services in a building may be provided for several different kinds of loads: lighting, motors, communications equipment. These loads may vary in voltage and times of service, as for example, continuous lighting or intermittent elevator motors. Motors have high instantaneous starting currents, which can be four to six times the running current, but which lasts only a brief time. It is highly improbable that all of the intermittent loads will occur at once. To determine the probable maximum load, demand factors and coincidence factors (diversity factors) must be applied to the total connected load (see Art. 15.8). Lighting Loads. The minimum, and often the maximum, watts per square foot of floor area to be used in design are specified by building codes for various uses of the floor area. Maximum wattages are set to conserve energy and should be followed wherever possible. Electrical engineers, however, may exceed the minimum wattages if the proposed use requires more. For example, lighting may be designed to give a high intensity of illumination, which will require more watts per square foot than the code minimum. (Recommended lighting levels are given in the Illuminating Engineering Society Lighting Handbook.) Power Loads. In industrial buildings, the process equipment is normally the largest electrical power load. In residential, commercial, and institutional buildings, the power loads are mainly air-conditioning equipment and elevators. Some commercial and institutional buildings, though, contain significant computer and communication equipment loads, and special attention is required to properly serve these electronic

Figure 16.14e shows a type of 2:1 roping suitable for slow, low-rise elevators. In contrast to the roping in Fig. 16.14c, only one end of the hoisting ropes is deadended at the top of the hoistway. The other end is attached to the counterweight. Also, the ropes pass around idler sheaves at the car that are placed on the underside of the car frame. 16.9.8 Elevator Operating Systems The method of actuating elevator control is called elevator operation. Many types of operation are available and some are complex and sophisticated. These may cost more than the simpler systems for installation and operation, but the sophisticated systems accomplish more automatically and handle traffic more efficiently. Following are descriptions of several types of operation: Car-Switch Operation. With a manually operated car switch or continuouspressure buttons in the car, an operator controls movement and direction of travel of the car. To ensure that the operator controls car movement, the handles of levertype operating devices should return to the stop position and latch there automatically when the operators hand is removed. In automatic car-switch, floor-stop operation, the operator releases the lever or button to stop the car at a landing. Slowing and stopping are then accomplished automatically. Signal Operation. The car can be started only by an operator pushing a start button in the car. The operator can register stops in advance by pressing and releasing a push button in the car corresponding to the predetermined floor number. Persons calling for the elevator can similarly register a stop by pushing an up or down hall button. The car automatically stops at landings for which signals were registered, regardless of the direction of car travel or of the sequence in which buttons at various floors were pressed. When a landing is served by two or more elevators, the first available car approaching the floor in the specified direction makes the stop automatically. Automatic Operation. An operator is not needed for automatic operation. Starts and stops are signaled by passengers in the car or by hall buttons or by an automatic operating mechanism. The car starts either in response to this mechanism or when a passenger presses a car or hall button. Responding to signals from car or hall buttons, the car travels to and stops at the signaled landings, and car and hoistway doors open automatically. Following, in order of increasing sophistication, are descriptions of several types of automatic operation. Single Automatic Operation. The car starts when a passenger presses and releases a car button corresponding to a landing. The car then travels to that floor and stops. The car also starts when a hall button is pressed, travels to that landing, and stops. After any button has been pressed, depression of any other button has no effect on car movement until the stop signaled by the first button has been made. Selective Collective Automatic Operation. When a car button corresponding to a landing is pressed, the car travels to that floor but also, on the way, makes other stops signaled. Hall calls are answered in the order in which landings are reached in each direction of travel, regardless of the sequence in which signals were received. Up calls are served when the car is traveling upward, and down calls are answered when the car is traveling downward. Group Automatic Operation. This is an extension of selective collective operation to a group of cars serving the same landings. A supervisory control system automatically dispatches cars to answer calls and coordinates the operation of the group. A call is answered by the first car to approach a landing in the proper direction. In response to a timer, the car leaves a terminal at predetermined intervals, which can be varied in accordance with traffic requirements. Group operation with automatic dispatching increases the number of passengers the elevators can carry

The industry approach to development of a definitive cost estimate for a warehouse using the crew development technique generally proceeds as follows: From the contract documents, the estimator determines the volume and footprint of the warehouse and the uses to which each area would be put, for example, offices, rest rooms, and loading docks. Assuming that one crew will be used to build the shell of the building and other crews to construct the interior areas, the estimator obtains the unit rates of production from standard production handbooks. (The production handbooks for facilities change only with the introduction of new equipment or materials.) Next, for each item taken off the contract documents, the estimator determines the unit costs of materials, labor, and equipment. Then, each unit cost is multiplied by the corresponding quantity of the item to be used. Finally, the estimator adds the products to obtain the total cost of materials, labor, and equipment for the warehouse. Estimators tend to use the industry approach with the crew development technique where labor costs are low or differences between costs of different crafts are


Website built by Justin O’Dea www.webdeveloperdocklands.com.au

xvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideos