Why work with us?

With over 20 years of bricklaying experience, the JRC team has built a strong reputation for cost effective and professional bricklaying solutions. We are fully licensed and insured, and our Melbourne bricklayers deliver specialist bricklaying and blocklaying services throughout the South Eastern Suburbs of Melbourne.

JRC have a demonstrated ability to run multiple projects and always supply enough labour to meet and exceed programme deadlines.

We're happy to travel

From Wantirna to Werribee we cover the Greater Melbourne area and continue to travel to do what we love. No job is too small or too big. We'll be there on time and with a professional approach to any job.

Services

We offer an extensive list of services to suit all requirements.

Bricklaying

At JRC our team of highly skilled and experienced tradesmen are capable with all aspects of Brickwork construction. We have the skills and processes in place to meet your exact requirements. We have a proven track record in the delivery of technically challenging projects. You will find our team easily accessible and willing to give advice through to the completion of your project.

Blocklaying

At JRC we have laid hundreds of thousands of square metres of perfect blockwork.

We have an experienced and fully trained workforce committed to providing quality workmanship whilst exceeding client expectations, delivered on time and on budget, within a safe environment.

JRC know what is expected of us and more importantly, our clients know what to expect from us, a consistent and professionally delivered service with a name built on honesty and quality.

We will service anywhere in Melbourne:

  • Sandringham
  • Caufield
  • Brighton
  • Elsternwick
  • Frankston
  • Cranbourne
  • Berwick
  • Pakenham
  • Dandenong
  • Belgrave
  • Bayswater
  • Wantirna

Special consideration must be given to the drainage of dry-pipe systems and portions of preaction systems subject to freezing. The branch lines of these systems should be pitched 1/2 in per 10 feet and mains 1/4 inch per 10 feet of length towards a suitable drain connection to accommodate total system drainage. Where trapped piping in dry-pipe systems exceeds 5 gallons capacity, a means must be provided to drain the trapped area without accidentally tripping the dry-pipe valve. This is usually accomplished with use of a drum drip assemble, an assembly which permits isolating trapped water and draining it without loosing air pressure. Inspectors Test Connections. All sprinkler systems should be tested periodically to ensure their proper function. A test connection for wet- and dry-pipe systems consists of a connection at least 1 inch in diameter with a test valve terminating in a smooth-bore, corrosion-resistant orifice. This orifice connection should be sized to provide a test flow equivalent to the smallest orifice size sprinkler installed in the system. For most systems the test valve connection can be located anywhere down stream of the alarm valve or flow switch, whichever is provided; however, on dry-pipe and double-interlock preaction systems the alarm test valve must be located at the hydraulically remote point of the system. This is to ensure that water will reach the remote end of the sprinkler system without undue delay, usually 60 seconds for large systems. Approvals of Sprinkler-System Design. In all cases, before a sprinkler system is installed or modified, the applicable drawings and hydraulic calculations should be submitted to the authority having jurisdiction and the insurance underwriter as nec- essary. Since beneficial reductions in insurance rates may be obtained by suitable installation of sprinkler systems, it is important that the underwriter have sufficient time for a full review of the plans before construction begins. Similarly, municipal approval of the sprinkler-system plans is necessary before the structure can be occupied. In actual construction, the installing contractor generally secures the necessary municipal approval. The existence of this approval should always be confirmed before construction starts. Standpipes, hose valve connections supplied with water from a piping system that is always under pressure or can be rapidly supplied with water under pressure are the usual means through which firefighters are provided water to fight interior fires in large buildings such as malls and high-rises. NFPA 14, Standpipe, Hose Systems, is the recognized standard for the installation and design of standpipe systems. Today, most standpipes installed are intended for use by the fire department; however, some are designed for occupant use. As with sprinkler systems, building codes generally dictate when and where standpipes are required. 14.30.1 Class of Service Standpipe systems are classified into the following types: Class I. For use by fire department personnel only. These systems are provided with 21/2-inch hose valves located in building stairwells and other protected areas. Water supplies permit two hose streams to be fed simultaneously from a single riser. Each stream provides 250 gal /min at a minimum pressure of 100 psi. Class II. For occupant use only. Provided with 11/2-inch hose valves and hose racks with a minimum 100-feet length of 11/2 hose, these standpipes are located in a building such that all areas of a building are within 130-feet of a hose valve (100- feet of hose plus 30-feet of water spray). It should be noted that most authorities having jurisdiction no longer permit hose to be attached to Class II systems since it is felt that the best option for occupants who are not trained in fire fighting procedures is to evacuate the building and report the emergency situation. Class III. A combination of Class I and Class II systems with both 21/2-in hose valves and 11/2-in hose valves and hose racks with 100 ft of hose, installed as required for a Class I and Class II system. The calculated water supply at an outlet is the same as for a Class I system. Riser Sizes. Standpipe pipe sizes can be established based on the performance of hydraulic calculations or for low rise buildings the NFPA 14 Pipe Schedule System, with the hydraulic procedure being the preferred method. The hydraulic calculations for a Class I system are based on flowing 500 gpm at 100 psi at the most remote standpipe and 250 gpm at the top hose connection of all other standpipes with a total not to exceed 1250 gpm. Maximum Pressure. Standpipe systems should be designed so the maximum gage pressure at the inlet of any Class I hose connection does not exceed 175 psi and Class II hose connection, 100 psi. Where pressures exceed 175-psi, pressure- limiting devices must be installed. Engineers must be extremely cautious in specifying pressure-limiting devices as they are frequently specified improperly. Water supplies for sprinkler and standpipe systems must be reliable. When a municipal water supply has been identified as unreliable or incapable of meeting the demand of a sprinkler or standpipe system, fire pumps and water storage tanks or reservoirs may be required. Even in instances where a water supply is reliable and the protected area is of high value, a secondary water supply employing water tanks and fire pumps is often provided. In determining the size and elevation of tanks, site conditions should be of primary concern. Often times water storage tanks can be located advantageously at the higher elevations of a property. Other times penstocks, flumes, rivers or lakes may serve as a water supply. In these cases approved strainers must be provided on the water supply inlets to prevent obstructions from entering system piping. In all cases, whether the water supply is from a municipal source or raw source as described above, consideration must be given to the potential effects of Microbiological Influenced Corrosion (MIC) which can rapidly damage sprinkler piping. While water supply adequacy is heavily reliant on the presence of sufficient flow and pressure, water supply duration is also important. For sprinkler systems the minimum water supply duration is 30, 60 and 90-minutes for light, ordinary and extra hazard areas, respectively. Standpipe water supply duration is 30-minutes. Water supply duration is mandated to ensure that adequate time is available to achieve fire control. Fire Department Connection. With the exception of small sprinkler systems, all sprinkler and standpipe systems must be provided with a fire department connection (FDC). The FDC, often referred to as the siamese connection, is a means through which fire hoses may be connected to a system to support the hydraulic requirements of the system to which it is attached. In most cases, the FDC is a backup water supply. It should be noted that often times the FDC for standpipes in lowrise buildings is the only source of water supply. These systems are referred to as manual standpipes. Before specifying a manual standpipe the AJH should be consulted. Depending on the AJH, FDCs may be installed on a side of a building or they may be free standing. Whatever the case, the FDC should be 18- to 36-inches above grade, and within clear sight of a fire department access-way. To speed fire ground operations it is good practice to locate FDCs within 75 feet of a fire hydrant. In addition, high rise buildings should be provided with two remotely located FDCs. While not a code requirement, as a rule of thumb, for each 250-gpm required, as determined in the hydraulic calculations, one 21/2-inch FDC outlet should be provided. For a 600-gpm-system demand three 21/2-inch FDC outlets should be provided. As it is becoming common place for fire departments to use quick connecting FDCs, Stortz Connections, and since the fire department is the FDC end user, in all cases the local fire official should be consulted regarding FDC type and location. Any mechanical device or system is more reliable if it is supervised or monitored. Sprinkler systems are designed to be rugged and dependable as shown by their impressive performance record; however, reliability improves where systems are monitored by an approved central-station supervisory service for valve position (open or closed) and water flow switch status. A central station monitors the equipment specified by the engineer and provided by the contractor and transmits appropriate signals over leased telephone lines or other approved methods, to a constantly attended location. When a signal is received at the central station, no matter what hour, the fire department and any other preestablished emergency contacts are summoned. When notification of a closed valve is provided, the building owner or other acceptable contact should investigate, but notification of water flow should always result in fire department dispatch. Monitoring services are available across the country and are arranged by contract, usually with an installation charge and a monthly maintenance fee. Requirements for such systems are in NFPA 72, National Fire Alarm Code. Where no such service is available, a local or proprietary substitute can be provided. Developing proficiency in the proper design and specification of fire sprinkler systems is extremely tedious. While sprinkler system design is admittedly a small portion of the engineering design package for a construction project, the implications of inadequate system design are more than severe. There have been numerous cases where engineers have been named in lawsuits relating to improperly designed automatic sprinkler systems. To obtain additional information regarding the proper design and installation of automatic sprinkler systems the NFPA or Society of Fire Protection Engineers (SFPE) are excellent resources. In addition, to display your proficiency in the field of fire protection engineering, registration as a fire protection engineer is available in most states.

With carpet and pad 48 8-in concrete slab 35 With carpet and pad 57 21/2-in concrete on light metal forms, steel bar joists 27 With carpet and pad 50 TABLE 11.30 Performance of Commonly Used Sound Absorbents Absorbent Thickness, in. Density, lb per cu ft Noise reduction coefficient Mineral or glass fiber blankets 1/24 1/26 0.450.95 Molded or felted tiles, panels, and boards 1/211/8 825 0.450.90 Plasters (porous) 3/83/4 2030 0.250.40 Sprayed-on fibers and binders 3/811/8 1530 0.250.75 Foamed, open-cell plastics, elastomers, etc. 1/22 13 0.350.90 Carpets Varies with weave, texture, backing, pad, etc. Draperies Varies with weave, texture, weight, fullness Absorption coefficient per sq ft of floor area at frequencies. Hz: Seated audience 0.60 0.75 0.85 0.95 0.95 0.85 Unoccupied upholstered (fabric) seats 0.50 0.65 0.80 0.90 0.80 0.70 Acoustical Absorbents. Sound absorption coefficients and noise reduction coefficients of acoustical absorbents, including carpets and other furnishings, are usually readily available from manufacturers. The coefficients are normally obtained from laboratory tests of panel specimens of about 72- to 80-ft2 area, tested according to ASTM C423. It is imperative that the test specimens be as nearly identical as possible, in construction system and detail, with actual field installations, since construction details enormously affect acoustical performance. Table 11.30 lists performance ranges of typical absorbent materials. For specific data on specific materials or systems, always refer to specific tests by accredited

Base Weld electrode 0.75 0.60FEXX 3.0  nominal tensile strength of weld metal * Reprinted with permission from F. S. Merritt and R. L. Brockenbrough, Structural Steel Designers Handbook, 2d ed., McGraw-Hill, Inc., New York. Design strength is the smaller of FBM and Fu: FBM  nominal strength of base metal to be welded, ksi. Fw  nominal strength of weld electrode material, ksi. Fy  specified minimum yield stress of base metal, ksi. FEXX  classification strength of weld metal, as specified in appropriate AWS specification, ksi. The effective throat thickness of a fillet weld is the shortest distance from the root of the joint to the nominal face of the weld (Fig. 7.3). For fillet welds made by the submerged-arc process, however, the effective throat should be taken as the leg size for welds 3/8 in and smaller but as the theoretical throat plus 0.11 in for larger fillet welds. For a complete-penetration groove weld, the effective throat is the thickness of the thinnest part joined. For partial-penetration groove welds, the effective throat thickness depends on the included angle at the root of the groove. For all J or U joints and for bevel or V joints with an included angle of 60 or more, the effective throat thickness may be taken as the depth of the chamfer. When the included angle for bevel or V joints is between 45 and 60, the effective throat thickness should be the depth of chamfer minus 1/8 in. For flare bevel and flare V-groove welds when flush to the surface of a bar or a 90 bend in a formed section, the effective throat thickness is 5/6 and 1/2 the radius of the bar or bend, respectively. When the radius is 1 in or more, for gas metal arc welding, the effective thickness is 1/4 the radius. Welds subject to static loads should be proportioned by ASD for the allowable stresses and by LRFD for the design strengths in Table 7.27. If connections will FIGURE 7.40 Bolted connection in shear and bearing: (a) with bolt in single shear; (b) with bolt in double shear (two shearing planes). be subject to fatigue from stress fluctuations, load capacity should be reduced as provided in the AISC Specification for Structural Steel for Buildings. When some slip, although very small, may occur between connected parts, the fasteners are assumed to function in shear. The presence of paint on contact surfaces is therefore of no consequence. Fasteners may be A307 bolts or high-strength bolts or any other similar fastener not dependent on development of friction on the contact


Website built by Justin O’Dea www.webdeveloperdocklands.com.au

xvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideosxvideos